Under general Health and Safety law, Approved Code of Practice (ACoP) L8, you must consider the risks from Legionella that could affect your employees or members of the public, and take suitable precautions.
Our Risk Assessments include :
We use the latest and highest quality products to treat and disinfect the water tank and including hot and cold water systems through to outlets.
EndoSan Silver peroxide is an eco-friendly, multi-component, oxidising biocide. A highly effective sanitising solution is formed utilising a stable combination of Hydrogen Peroxide and Silver ions. This combination is so effective that it creates a biocide 20 times more powerful than that of hydrogen peroxide. Other benefits include:-
TMV or Thermostatic Mixer Valve is a device that is designed to control water temperature for showers, baths and outlets. These devices require servicing on a regular bases in order for them to function correctly. We offer servicing and installation of both type 2 and type 3 TMV's. To comply with Legionella prevention guidance; water must be stored at no less than 60 degrees and distributed at no less than 50 degrees, however where the risk of scalding has been identified . TMV's are fitted to regulate the temperature at the outlets.
Here at Pure Clear Water we offer bacteria sampling using a high performance hand held ATP meter. It is designed for the rapid testing and detection of contamination in water and on surfaces caused by unwanted bacteria, allergens and food residue.
Our hand held ATP meter is designed using state-of-the-art electronics making it simple and easy to use. It offers incredible sensitivity, much improved functionality and excellent value for money and is ideal for use in any application where the rapid detection of contamination in water or on surfaces is critical. We can also offer a comprehensive suite of laboratory tests including UKAS-accredited legionella analysis, sampling and water quality tests for landlords, building owners and operators, facilities managers, duty holders and the responsible person. Which would give you a comprehensive result of exactly what is or isn't n your water system.
An inspection for scale and sediment in the cistern must be carried out on an annual basis or where the water quality seems to be cloudy. The sedimentation, scale etc. will settle down in the calorifiers and will provide an environment for Legionella growth, therefore the cleaning and disinfection of this storage vessel must be carried out. If there is no inspection hatch available, the system must be flushed thoroughly on regular intervals to avoid the formation of scale and debris in the base of the storage vessel.
For calorifiers with no access hatch a sample of drain water should be taken for bacteria sampling and its condition noted.
Shower head descaling and disinfection is required on a quarterly basis and is important to keeping your water system free from bacteria and scale. Which would not only help shower heads last longer and function better, but also alleviate the risk of contracting bacteria though the air born water droplets which is the most common way of contracting water born diseases.
Schematic drawings form an integral part of any comprehensive legionella risk management programme and are a specific requirement of the Health & Safety Executive’s procedures dealing with the control of legionella bacteria in water systems. Schematic drawings of water systems are intended to be easy to read without specialised training or experience and should incorporate the important components that make-up an engineered water system, but leave out those elements that are considered to be irrelevant.